Product Features:
1) Ultra-Wide Temperature Adaptation
The temperature adaptation range is -38 to 38℃. Compared to ordinary and anti-freeze eyewash stations, it can prevent pipeline freezing in extremely cold environments, meeting the emergency needs of ultra-low temperature scenarios such as northern winters and polar operations.
2) Dual-Function Integrated Design
It integrates eyewash and shower functions. The push-type eyewash device provides a flushing flow of ≥11.4 L/MIN, and the pull-type shower device provides a flushing flow of ≥76 L/MIN, which can respectively handle chemical splashes to the eyes/face and body/clothing.
3) Corrosion-Resistant Material Guarantee
Core components such as the shower head, eyewash elbow, and valve body are all made of SS304 stainless steel, which is resistant to chemical corrosion and suitable for use with potable tap water as the flushing liquid, avoiding secondary pollution.
4) Explosion-Proof Safety Configuration
The junction box, sound and light alarm, and electric heating cable are all explosion-proof designs, with an explosion-proof rating of Exd IIC T6/Exe IIC T6 and a protection level of IP66, suitable for flammable and explosive chemical and oil and gas extraction scenarios.
5) Intelligent Alarm Linkage
When using the eyewash or shower function, it will automatically trigger a sound and light alarm and transmit a switch signal to the DCS system, facilitating timely response and rescue dispatch by on-site personnel.
6) Convenient Installation and Transportation
The inlet and outlet use standard industrial interfaces, and the bottom is equipped with a sturdy SS304 base, which can be directly connected to the on-site pipeline; it uses wooden box packaging, with two units per package, facilitating batch transportation and on-site deployment.
Application Scenarios:
• Chemical plants in cold northern regions: To deal with chemical splashes such as hydrochloric acid and caustic soda, the electric heating function ensures that the pipeline does not freeze in winter.
• Oil and gas extraction and refining sites: The explosion-proof design prevents accidents caused by electrical sparks, providing emergency flushing protection for workers.
• Low-temperature laboratories and pharmaceutical workshops: To deal with liquid nitrogen and low-temperature reagent splashes, the stable temperature adaptability ensures the normal operation of the equipment.
• Polar outdoor operation bases: In polar scientific research, Arctic mining areas, and other scenarios, it provides immediate flushing protection for personnel in extremely low temperatures.
| Ambient temperature |
-40~38°C |
| Operating temperature |
16~38°C (Guaranteed by site) |
| Inlet size |
1-1/2" RF-FLANGE-ASME-B16.5-CL150# |
| Outlet size |
1-1/2" FNPT |
| Operating pressure |
0.2~0.4 MPa |
| Washing liquid |
Tap water for drinking |
| Shower water flow |
> 76 L/MIN |
| Eye wash and Face wash water flow |
> 11.4 L/MIN |
| Washing Time |
> 15 MIN |
| The material of the unit |
| Shower (S3) |
SS304 |
| Eyewash elbow (E2) |
SS304 |
| Eyewash bowl (B2) |
SS304 |
| Shower valve |
SS304, Size: 1" |
| Eyewash valve |
SS304, Size: 1/2" |
| Pipe |
SS304 |
| Base |
SS304, Size: 300*300*10.0mm |
| TECHNICAL PARAMETERS OF ELECTRICAL INSTRUMENTS |
| Voltage of the heating traced cable |
220VAC/230VAC |
| Size and type of power interface |
M25*1.5, SS304, Normal type cable gland (for heating trace cable power supply) |
| Explosion-proof and protection level of the junction box, Alarm, Tc, and Limit switch |
Exd IIC T6, IP66 |
| Explosion-proof and protection level of heating trace cable |
Exe IIC T6, IP66 |
| The power of heating trace cable |
150W |
| Static grounding to the wire post |
M10 |
| Operation method |
| Shower |
Hand push |
| Eye/face wash |
Hand push |
| Packing size and weight |
| Packing and size (2 units per package) |
Wooden case packaging, L*W*H = 265*100*500 mm |
| Weight (2 units per package) |
100 KG |